Formlabs Logo

Power requirements for the Fuse X1 ecosystem

Power requirements for the Fuse X1 ecosystem

Fuse X1

The Fuse X1 requires a dedicated single phase AC circuit, rated for 50 A at 200–240 VAC, as well as reliable grounding.

The Mix Kit requires a dedicated single phase AC circuit, rated for 40 A at 200–240 VAC 50Hz, as well as reliable grounding.

Notice:

The circuit for the Fuse X1 printer must be separate from other devices, including the corresponding Fuse Sift X1, fans, vacuums, power tools, space heaters, or any large appliances or power tools. Power surges may disrupt prints and/or permanently damage sensitive components, jeopardizing the reliability of the product.

Actual power consumption during a print will depend on environmental conditions, print settings, and print geometry, but will generally be at or below 36 A.

The Fuse X1 has a lockout-capable main disconnect switch located at the rear of the machine.  Always disconnect power before performing any electrical maintenance to the machine.

When using a nitrogen generator, which requires a compressed air source, connect the air compressor to a separate electrical circuit from the printer.

Fuse Sift X1

The Fuse Sift X1 requires a dedicated AC circuit, providing at least 20 A at 120 VAC (NA) or 10 A at 230 VAC (EU), as well as reliable grounding.

Notice:

The circuit for the Fuse Sift X1 must be separate from other devices, including the corresponding Fuse X1, fans, vacuums, power tools, space heaters, or any large appliances or power tools. Power surges may disrupt prints and/or permanently damage sensitive components, jeopardizing the reliability of the product.

Maximum vacuum current draw

Required circuit amperage

<6 A (230 VAC)

<12 A (120 VAC)

10 A (230 VAC)

20 A (120 VAC)

≥6 A (230 VAC)

≥12 A (120 VAC)

12.5 A (230 VAC)

25 A (120 VAC)